Digital controller for heating systems with remote control, DIN-rail mounting (9 modules)
-
DESCRIPTION
General features0
The unit regulates water delivery temperature of the heating systems.
It is suitable for all heating systems types of apartment buildings, factories, schools, cottages, etc.- Control of the circulation pump (with shut-down delay).
- Control of one ON-OFF auxiliary user (domestic water).
- 1 RS232 communication channel for connection to a modem o directly to a PC.
- Weekly programming with 3 time bands per day.
- Automatic switching from summer time to winter time and vice versa.
- Recorder of the temperatures and events of the last 48 hours (datalogger).
- Visualization of all preset temperatures and parameters.
- LED to indicate relays status.
- Clock charge reserve: over 5 years.
- Alphanumeric display with 2 lines each with 16 characters with timed backlighting.
- All functions are executed through the menu.
- Removable terminal board for easy wiring.
Electric features- Power supply: 230Vca 50Hz.
- Consumption: 7 VA.
- Contacts rating: 5A- 230Vca (resistive load).
- 4 optoisolated alarm inputs to prevent interference.
- 1 communication channel RS232 for connection to a modem or directly to a computer.
-
ADVANTAGES
0
The unit regulates water delivery temperature of the heating systems.
It is suitable for all heating systems types of apartment buildings, factories, schools, cottages, etc.Advantages -
TECHNICAL SPECIFICATION
CODE CONTACT RATING OPERATING TEMPERATURE CONSUMPTION PROTECTION DEGREE EV85 5(3)A - 250Vac 0 ÷ 50 °C 7 VA IP40 back panel -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with the law 373, law n.10 dated 9 of January 1991 and D.P.R.412 dated 26 of August 1993.
- Complies with EN 60730-2-9; EN 60730-2-7 standards.
Installation and use- DIN-rail mounting (9 modules).
- To ensure an adequate protection install the device on the DIN-rail within a framework.
- The removable terminals facilitate the wiring and a possible replacement.
The controller calculates the delivery temperature value as a function of the following parameters:
- external temperature (detected by the probe);
- regulation broken curve (set);
- ambient temperature calculated by the controller (optional);
- ambient temperature detected by the ambient probe (optional).
By means of controller it is possible to choose the desired output type:
- mixing valve control (relay “opens” and “closes”);
- 2-stage output (relay “opens”=stage 1 and “closes”=stage 2);
- 4-stage output (relay “opens”=stage 1, “closes”=stage 2, “pump”=stage 3 and “aux”=stage 4).
N.B. with 4-stage operation the two relays (pump control and auxiliary) cannot be used for another purposes.
It compares the theoretical (calculated) delivery temperature value with the real value, measured by the relative probe and acts on the regulation valve to obtain the desired temperature.
Programming can be made via GSM phone.
- TECHNICAL LITERATURE
-