Thermal energy calculator split version
-
DESCRIPTION
General features0
Separate (split) thermal energy calculator easily connectable to external flowmeters equipped with pulse output and to be installed on sites where because of pipe sizes larger than ¾” or hard to reach places, the compact heat meter cannot be used.
- The ECCM33 calculation unit is equipped with distinct sections capable of simultaneously accounting for:
– thermal energy of a heating circuit
– thermal energy of a cooling circuit
– volume of the domestic cold water meter
– volume of the domestic hot water meter - The unit has been designed to facilitate installation and reduce commissioning times. The ECCM33 unit is equipped with a wired “M-Bus” communication line and a wired “Local Bus” communication line with proprietary protocol to allow consumption to be consulted by the user via compatible Fantini Cosmi chronothermostats or HBES systems .
- Dimensions: 154 x 119 x 51 mm
- Protection degree: IP52
- Environmental class: A (E1, M1)
- Maximum power 99 MW
- Measurement temperature range (heating): 5÷180°C
- Temperature range difference (heating): 3÷150K
- Measurement temperature range (cooling): 2÷24°C
- Temperature interval difference (cooling):: 3÷20K
- Display levels: 6
- Display: 8 character LCD + icons
- Energy indication: MWh
- Maximum impulse cable length: 2 m
- Temperature sensor type: Pt 1000
- Temperature sensor cable length: 3 m/ 10 m
- Input pulse value: 0.1 – 0.25 – 1.0 – 2.5 – 10 – 25 – 100 – 250 liters
- Pulse inputs: 1 dedicated for the heating/cooling circuit meter, 2 dedicated to additional pulse output meters (sanitary)
- Pulse output: 1 heating output, 1 cooling output
- Pulse input class: Class IA (default): Open Collector or reed contact, max 5Hz
- Maximum pulse input frequency (MID certified): 5Hz
- Flow meter installation (flow in): Return piping
- Supported liquid: Water
Electric features- Battery powered
- Nominal battery voltage: 3.6V
- Battery type: Li-SoCl2 Lithium Thionyl Chloride
- Temperature measurement range: 5 ÷ 180 °C
- Maximum battery life: 10 + 1 years, depends on the type of use
- The ECCM33 calculation unit is equipped with distinct sections capable of simultaneously accounting for:
-
ADVANTAGES
0
Separate (split) thermal energy calculator easily connectable to external flowmeters equipped with pulse output and to be installed on sites where because of pipe sizes larger than ¾” or hard to reach places, the compact heat meter cannot be used.
Advantages -
TECHNICAL SPECIFICATION
CODE Power supply Temperature measuring range Temperature sensor Protection degree Pulse inputs Pulse outputs Communication ECCM33 litium battery 3,6V 5 ÷ 180 °C PT1000 IP52 n.2 pulse inputs n.2 pulse outputs M-Bus ECCM33R litium battery 3,6V 5 ÷ 180 °C PT1000 IP52 n.2 pulse inputs n.2 pulse outputs M-Bus/ M-Bus WIreless -
HOMOLOGATION AND INSTALLATION
Homologation
- Approved according to the MID 2014/32/UE MI004 standard and the EN1434 standard.
Installation and useThe thermal energy calculation unit must be connected to a meter
installed on the system return pipe.SEE UNDER: EXAMPLE OF INSTALLATION ON RETURN PIPE.
- The ECCM33-ECCM33R calculation unit is equipped with dedicated sections for the measurement of thermal energy of a heating/cooling circuit and the measurement of the volume given by the domestic hot and cold water meters.
- The calculation unit is suitable for domestic applications with two-pipe systems, in a boiler room or any other compatible application.
- In residential systems, usually with two pipes, the measurement of thermal energy takes place on a single section in both heating and cooling regimes.
- TECHNICAL LITERATURE
-