Temperature probes for electronic control units
-
DESCRIPTION
General features0
Temperature probes are used for receiving the necessary information for the electronic control units operation.
EC11-EC14 EXTERNAL PROBES
- Case in thermoplastic material.
- Linearized NTC thermistor heat-sensitive element.
- Bipolar terminal board.
- G1/4” cable gland
EC12-EC15 CONTACT DELIVERY PROBES
- Case in thermoplastic material.
- Linearized NTC thermistor heat-sensitive element.
- Bipolar terminal board.
- G1/4” cable gland.
- Plastic clamp that can be reused for fastening to the pipe.
EC13-EC16 IMMERSION DELIVERY PROBES
- Case in thermoplastic material.
- Linearized NTC thermistor heat-sensitive element.
- Bipolar terminal board.
- G1/4” cable gland.
- Metal protection sheath with G1/2 conical connection for pressure seal.
EC17 WELL PROBE
- NTC10K temperature probe.
- Brass capsule 6x35mm. Double insulation bipolar cable (white-red inside, grey outward) with 2×0,35mm² cable section, length=1,5 meters.
- Tinned terminals. Insulation: >100mohm @500vca.
EC19 FLOOR PROBE
- NTC10K temperature probe.
- Nylon capsule 7x25mm.
- Double insulation PVC bipolar cable (white outward) with 2×0,50 mm² or 2×0,35 mm² cable sections, length=3 meters.
- Tinned terminals. Insulation: >100mohm @500vca.
EC21 PROBE FOR SOLAR PANELS
- Stainless steel capsule 3x60mm.
- Bipolar cable in ptfe.
- 2×0.15mm² cable section, length = 1.5 meters.
- Terminals: previously insulated leads. Insulation: >20Mohm @500Vac.
-
ADVANTAGES
0
Temperature probes are used for receiving the necessary information for the electronic control units operation.
Advantages -
TECHNICAL SPECIFICATION
CODE PROBE TYPE CONTROLLED LIQUID MAX. TEMPERATURE FOR EC11 external probe -40 ÷ 80°C EV02F - EV05M EC12 contact flow probe -40 ÷ 120°C EV02F - EV05M EC13A immersion flow probe -40 ÷ 150 C EV02F - EV05M EC14 external probe -40 ÷ 80°C EV83 - EV70D - EV80 - EV84A EV85 - EV87 - EV90 - EV91 EC15 contact flow probe -40 ÷ 120°C EV60 - EV83 - EV70A - EV70D - EV80 - EV80E - EV84A EV85 - EV85E - EV87 - EV90 - EV91 EC16A immersion flow probe -40 ÷ 150 C EV60 - EV83 - EV70A - EV70D - EV80 - EV80E - EV84A EV85 - EV85E - EV87 - EV90 - EV91 EC17 well probe -30 ÷ 85 °C EV60 - EV83 - EV70A - EV70D - EV80 - EV80E - EV84A EV85 - EV85E - EV87 - EV90 - EV91 EC21 probe for high temperatures -40 ÷ 280 °C EV40 -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with EN 60730-2-9 standard.
Installation and use- EC11-EC14 EXTERNAL PROBES
Install the external probe on the north or north-east side at the half-height of the building, away from protruding sections, windows, doors, ventilation grilles, etc. - EC12-EC15 CONTACT DELIVERY PROBES
Install the contact probe on the water delivery pipe and downstream of the mixing valve, to a minimum distance of 1,50 meters from the valve and possibly after a pipe elbow. The contact probe should be mounted by interposing the heat conducting paste between the surfaces involved, while making sure adherence is good. - EC13A-EC16A IMMERSION DELIVERY PROBES
Screw the probe into the curve provided on the water delivery pipe, downstream of the mixing valve with a minimum distance of 1,5 meters.
- The temperature probes are the detectors through which the control units receive the necessary information for their operation.
- The sensing element consists of NCT linearized thermistors, therefore no part is moving and isn’t subjected to mechanical wear.
- TECHNICAL LITERATURE
-