Rear panel thermostats for remote mounting
-
DESCRIPTION
General features0
Thermostats with capillary for rear panel mounting to adjust the water temperature in the boilers, in the airconditioning and cooling systems, in household appliances, in electrical furnaces.
- Knob and ring to be bought separately
- Sensing element with stainless steel diaphragm.
- Copper bulb and capillary.
- Copper bulb and capillary, tinned for types C02C2 and C02D2.
- Screws for rear panel mounting for C02C2 and C02D2.
- Base in shock-proof self-extinguishing thermoplastic material V0.
- Threaded connection “Faston” 6.3 mm.
ACCESSORIES
- Code 2724259: control knob for C02A3
- Code 2724260: control knob for C02B3
- Code 2723094: control knob for C02C2
- Code 2723095: control knob for C02D2
- Code 2724261: control knob for C02E3
- Code 2723856: control knob for C02F
- Code 2554972: thermoplastic ring for control knobs
- Code 2754975: stainless steel ring for control knobs
- Code G23: seal cap Gc 1/2, PN10 bar, without casing.
- Code G28: copper sheath Gc 1/2 PN10 bar, length 177 mm, including spring to mount the capillary.
- Code 5677050: group of range limiters, used for knobs.
Electric features- Two directions microswitch of instant action with AGcdO contacts.
- Contact parameters in compliance with EN 60730-1: 15(6)A 250V~ 50Hz
-
ADVANTAGES
0
Thermostats with capillary for rear panel mounting to adjust the water temperature in the boilers, in the airconditioning and cooling systems, in household appliances, in electrical furnaces.
Advantages -
TECHNICAL SPECIFICATION
CODE TEMPERATURE RANGE DIFFERENTIAL MAXIMUM BODY TEMPERATURE MAXIMUM BULB TEMPERATURE CAPILLARY LENGTH C02A3 10 ÷ 90 °C 6 ± 1 K 85 °C 150 °C 1 m C02B3 50 ÷ 300 °C 8 ± 2 K 85 °C 330 °C 1.5 m C02C2 - 20 ÷ 40 °C 2 ± 0.5 K 85 °C 80 °C 1.5 m C02D2 - 35 ÷ 20 °C 2 ± 0.5 K 85 °C 80 °C 1.5 m C02E3 40 ÷ 120 °C 6 ± 2 K 85 °C 150 °C 1 m C02F 50 ÷ 320 °C 10 ± 2 K 85 °C 330 °C 1 m -
HOMOLOGATION AND INSTALLATION
Homologation
- Compliance with standards EN 60947-5-1, EN 60730-1
- Compliance with Directive 2014/68 / EC (PED);
- ENEC certificates.
Installation and use- Rear panel mounting for the thermostat’s body.
- The bulb with capillary can be mounted remotely and is provided with seal caps or copper sheath with GC 1/2 connection
- When the temperature increases: 1-2 are opening, 1-4 are closing.
- Liquid expansion function.