Electronic control unit for gas leak detection with 1 detection zone
-
DESCRIPTION
General features0
Electronic control unit for gas leak detection in industrial environment, suitable for controlling and signaling dangerous gas concentration in the air, specifically for detecting methane gas, LPG and carbon monoxide.
- Light signals: 1 red LED, power supply ON; 1 yellow LED, failure; 1 red LED, gas alarm.
- Acoustic signals: 1 buzzer with sound intensity > 60db at 1m
- 1 button to reset the alarms and for testing the probe.
- Self-extinguishing plastic housing.
- Dimensions: 105 x 90 x 58 mm – 6 modules complies with DIN 43880 standard.
- Unit weight: 0.185 kg.
- Rear panel mounting on Omega DIN EN 50022 rail.
- Protection: IP20; IP40 when is properly installed in an electrical box.
- Environment temperature: 0 ÷ 50 °C.
- Environment humidity ±90% U.R. without condensation.
Electric features- Power supply: 12 Vac/dc ± 10%.
- Absorption: approximately 160mA (320mA) with a single probe; 460mA (620mA) with faulty probe and output.
- Connection with 2 terminals of 2.5 mm².
- Protection: input – fuse power supply 1A 5x20mm.
- 1 input for sensors S81, S82, S83, or probes ATEX S84, S85, S86 (different gas types).
- Connection to the probe with 3 terminals of 2.5 mm²: C (-12…24V); S (+4…20mA); A (+12…24V).
- Maximum connection length 50 m.
- Section of 3 conductors: 1.5 mm².
- Alarm output: n.1 relay with 1 SPDT contact 8A 250Vac.
- Failure output: n.1 open collector 12Vdc / 300mA max.
- Outputs connections: n.3 terminals of 2.5 mm² for relay C-NC-NO; n.2 terminals of 2.5 mm² for open collector.
-
ADVANTAGES
0
Electronic control unit for gas leak detection in industrial environment, suitable for controlling and signaling dangerous gas concentration in the air, specifically for detecting methane gas, LPG and carbon monoxide.
Advantages -
TECHNICAL SPECIFICATION
CODE POWER SUPPLY CONTACTS RATING CONNECTED SENSORS OPERATING AMBIENT TEMPERATURE PROTECTION DEGREE P81 12 Vac or 12/14 Vdc 5A - 250V 1 - 10 ÷ 50 °C IP40 -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with the standards EN 61779-1-4; CEI 216-5/1 Directives/Norms EMC EMC 89/336/CEE, Norm EN 50270.
Installation and use- Rear panel mounting on Omega DIN EN 50022 rail.
- It can be installed on the bottom panel or DIN modular panels.
- To ensure the proper protection degree of the device is necessary to install the unit in an electric box created according to current regulations for the workplace and within which can also be housed the power supply system.
- P81 control unit allows you to connect a probe model S81-82-83 or ATEX S84, S85, S86 probes for the construction of gas detection systems in environments such as boiler rooms, garages, warehouses, workshops, etc., with the possibility to control a solenoid valve or an auxiliary device (siren, flashing light, extractor, etc..) through inside alarm relay.
- The control unit must be powered at 12 Vac/dc.
- The functioning logic, selected by means of jumper E1, can be either positive or negative. The device reports its operation status through the LED.
ACCESSORIES
- S81: Sensor for methane gas detection.
- S82: Sensor for LPG gas detection.
- S83: Sensor for carbon monoxide detection.
- S80: Emergency signaling device with fixed light and continuous sound.
- S84: Probe for methane gas detection, certified with ATEX II 2G Ex d IIC T6.
- S85: Probe for LPG gas detection, certified with ATEX II 2G Ex d IIC T6.
- S86: Probe for carbon monoxide detection, certified with ATEX II 2G Ex d IIC T6.
- ZD… : Normally closed electromagnetic valves, with quick closing and opening, class a with approval.