Strap-on pipe thermostat
-
DESCRIPTION
General features0
Thermostat to control water temperature in heating pipe installations, for example to switch-off the circulation pump when the water temperature has dropped or to switch-on the air heater when the water temperature reaches the set value.
- Sensing element with stainless steel diaphragm, including support with hooks for the elastic metallic tape (included in the
package). - Base, cover and knob in shock-proof self-extinguishing thermoplastic material V0.
- Electrical connection output with PVC cable gland.
- Storage and transport temperature: -35 ÷ 120 °C.
- Differential 8 K (the differential is subtracted from the range value, the differential values refer to a thermal gradient of 6K/hour)
- Unit weight: 0,16 Kg.
- Protection level: IP40.
Electric featuresTwo directions microswitch of instant action with AGcdO contacts.
Contact parameters in compliance with EN 60730-1: 15(6)A 250V~50Hz. - Sensing element with stainless steel diaphragm, including support with hooks for the elastic metallic tape (included in the
-
ADVANTAGES
0
Thermostat to control water temperature in heating pipe installations, for example to switch-off the circulation pump when the water temperature has dropped or to switch-on the air heater when the water temperature reaches the set value.
Advantages -
TECHNICAL SPECIFICATION
CODE REGULATION TYPE TEMPERATURE RANGE DIFFERENTIAL ADMISSIBLE BODY TEMPERATURE MAXIMUM BULB TEMPERATURE C01A external 20 ÷ 90 °C 8 K 85 °C 120 °C C01B * external 10 ÷ 60 °C 8 K 85 °C 120 °C C01AM * external with manual reset 20 ÷ 90 °C 8 K 85 °C 120 °C C01ARI * internal 20 ÷ 90 °C 8 K 85 °C 120 °C * delivery time and minimum purchase quantity upon request *The differential is subtracted from the range value. The differential values refer to a thermal gradient of 6K/hour, 1K/min with heat-conducting paste bags -
HOMOLOGATION AND INSTALLATION
Homologation
- Compliance with standards EN 60947-5-1, EN60730-1;
- Compliance with Directive 2014/68 / EC (PED);
- ENEC certificates.
Installation and use- Installation on the pipeline through the elastic metallic tape, supplied with a length of 26 cm.
- Heat-conducting metallic paste for heat exchange improvement (on request).
- When the temperature increases: 1-2 are opening, 1-4 are closing.
- Liquid expansion function.
- Temperature measurement by means of the direct contact located between the pipeline surface and the sensing element (may be used a heat-conducting metallic paste, available on request).
- TECHNICAL LITERATURE
-
FAQS