Regulation control unit for heating systems, DIN-rail mounting (6 modules)
-
DESCRIPTION
General features0
Suitable for all central heating systems, such as those related to residential buildings, schools, hospitals, factories etc.
EV83 controller allows complete control of the mixing valve, or alternatively, the two-stage burner and the corresponding circulation pump.
- Alphanumeric display and 4 functional keys for parameters easy setting.
- Data setting via menu.
- Digital weekly programmer clock with charge reserve of approximately 5 years.
- Anticondensation probe for boiler protection.
- Three points control output for mixing valves with servocontrol type: O24 – O34 – O35.
- Three points control output for motorized mixing valves type: Z20 – Z30 – ZL30 – Zl31.
Electric features- Power supply: 230Vca 50Hz.
- Consumption: 3 VA.
- 3 output relays.
- Contacts rating: 5A-230Vca (resistive load).
-
ADVANTAGES
0
Suitable for all central heating systems, such as those related to residential buildings, schools, hospitals, factories etc.
EV83 controller allows complete control of the mixing valve, or alternatively, the two-stage burner and the corresponding circulation pump.
Advantages -
TECHNICAL SPECIFICATION
CODE POWER SUPPLY CONTACTS RATING OPERATION ADMISSIBLE TEMPERATURE PROTECTION DEGREE EV83 230Vac 50 Hz 5A - 250Vac 0 ÷ 50 °C IP40 (back panel) -
HOMOLOGATION AND INSTALLATION
Homologation
- Complies with the law 373, law n.10 dated 9 of January 1991 and D.P.R.412 dated 26 of August 1993.
- Complies with EN 60730-2-9, EN 60730-2-7 standards.
Installation and use- DIN-rail mounting (6 modules).
- To ensure an adequate protection install the device on the DIN-rail within a framework.
- The removable terminals facilitate the wiring and a possible replacement.
- EV83 purpose is to obtain a certain ambient temperature, starting from delivery temperature and external temperature reading.
The ambient temperature is set by the user through the configuration menu shown on the display and can take different values depending on the selected program. - In the moment when it has been recognized a program type the device calculates the delivery temperature required to obtain the ambient temperature associated with the same program; this is going to be calculated by interpolation using the preset delivery temperature values for four external temperature values ( -10°C, 0°C, 10°C, 20°C). It is possible to optimize the temperature control using the temperature probe EC10.
- See more details on technical data sheet.
ACCESSORIES
- EC10: ambient probe;
- EC14: external probe;
- EC15: contact delivery probe with clamp for fixing on the pipe;
- EC16: immersion delivery probe with protection casing and conic thread connection G 1/2.
- TECHNICAL LITERATURE
-
FAQS