High-efficiency dual-flow ventilation unit for ceiling and false ceiling installation. Airflow capacity from 500 to 8500 m³/h
-
DESCRIPTION
General features0
High-efficiency dual-flow ventilation unit for ceiling and false ceiling installation. Airflow capacity from 1600 to 8500 m³/h
- Equipped with cross-flow or counterflow high efficiency heat exchanger (minimum 73% with dry air and 80% with moist air), in accordance with Directive 2009/125/CE (Eco Design), regulation n. 1253/2021
- Equipped with single-phase and three-phase EC (high
efficiency) electrical fans whose speed can be adjusted
using a 0-10V signal thanks to their built-in control unit - Each fan speed can be adjusted step by step and
independently of the other - Two temperature sensors, one for supply air and one
for exhaust air - A by-pass motorized damfor (IP 54 actuator) can be
controlled either manually or automatically - Pressure switch that monitors the status of the filters
installed on the supply side - Control card prepared for the connection of a CO2
probe or humidity probe (both are optional) - Casing made of double panel galvanized steel sheets.
- Casing is made of aluminum profile and double panel
in galvanized steel, each filled with 23 mm thick
polyurethane (40 kg/m3) for thermal and acoustic
insulation - Equipped with a condense discharge drop tank. A
plastic, transparent tube extending for about 50 mm
outside the unit is connected to such drop tank, so
that it is possible to connect the unit to an external
condense discharge tube - Circular connections with supply and exhaust ducts
can be fixed on each side of the HRU, thus easing
installation of the machines - Air filters can be easily inspected and removed thanks
to dedicated hatches built in the unit cover - Where necessary, air filters are compatible with RITE
regulation (F7/F8/F9 classes) - Electric control panel installed on IP55. All units can
be mounted/installed outdoor when they are equipped
with a cover - Easy installation thanks to the “plug and play” system
- Predisposition for the use of constant flow/ pressure kit
-
ADVANTAGES
0
High-efficiency dual-flow ventilation unit for ceiling and false ceiling installation. Airflow capacity from 1600 to 8500 m³/h
Advantages -
TECHNICAL SPECIFICATION
CODE MODEL m³/h max Pa max W A V~ Hz Ph Motor class dB(A) Sound power AP20600 UVR 500 MF HE DP 500 340 337 2,61 230 50/60 1 F 52,6 AP20602 UVR 700 MF HE DP 700 450 607 4,9 230 50/60 1 F 56 AP20604 UVR 1200 MF HE DP 1200 380 300 x 2 1,4 x 2 230 50/60 1 F 53 AP20606 UVR 1600 MF HE DP 1600 550 500 x 2 2,2 x 2 230 50/60 1 F 54 AP20608 UVR 2300 MF HE DP 2300 550 680 x 2 2,9 x 2 230 50/60 1 F 58 AP20610 UVR 2800 MF HE DP 2800 550 900 x 2 4,2 x 2 230 50/60 1 F 61 AP20612 UVR 3200 MF HE DP 3200 650 1000 x 2 4,5 x 2 230 50/60 1 F 61 AP20614 UVR 3800 MF HE DP 3800 400 1500 x 2 7,5 x 2 230 50/60 1 F 61 AP20616 UVR 4500 MF HE DP 4500 650 2000 x 2 8,5 x 2 230 50/60 1 F 61 AP20618 UVR 5400 MF HE DP 5400 1400 2200 x 2 3,9 x 2 230 50/60 1 F 71 AP20620 UVR 6500 MF HE DP 6500 1200 2310 x 2 9,4 x 2 230 50/60 1 F 72 AP20622 UVR 7100 MF HE DP 7100 1100 2370 x 2 9,3 x 2 230 50/60 1 F 74 AP20624 UVR 8500 MF HE DP 8500 830 2380 x 2 9,8 x 2 230 50/60 1 F 77 -
HOMOLOGATION AND INSTALLATION
Homologation
In accordance with the 2009/125/CE Directive and Regulation
no. 1253/2014 (Ecodesign 2018)Installation and useCeiling or false ceiling mounting